Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/12/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FOR C OF O |
| 08/08/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) REMOVE UNION FROM GAS LINE ON ROOF. CLAMP GAS PIPE TO BLOCKS ON ROOF. PROVIDE ROOF JACKS AT ROOF PENETRATIONS. RE-TEST GAS SYSTEM. 2) BLOCK AND CLAMP CONDENSATE DRAIN LINE EVERY 4'. 3) INSTALL VENT ON WATER HEATER. EXTEND VENT 2' ABOVE WALL ON ROOF. 4) CONDESATE DRAIN CONNECTION AT LAV. NOT ADEQUATE. PROVIDE HOSE CLAMPS AND PROPER SIZE FITTING AT HOSE CONNECTION. |
| 08/06/2003 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ CANCELLED |