Permit: T02CM03749

Parcel: 118050020


Addresses:

1665 S LA CHOLLA BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/18/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
06/13/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) ITEM #3. THIS HAS NOT BEEN ADDRESSED
05/01/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*IMC 606.2.1. SMOKE ALARMS LOCATE IN RET. AIR DUCTING. CONDENSOR #3. REFRIG. PIPING, ELECT COND. ETC. BLOCKING CLEAR ACCESS TO SERVICE PANEL, HEAVY CAST IRON COMP. IN UNIT.
RM #121 ROOF TOP CONDENSER ON ROOF. ROOF. MATL. (JUNKED OUT) STORED ON TOP OF UNIT REMOVE THIS MATERIAL BEFORE WIND BLOWS IT ON TOP OF COND. FAN DISCHARGE.
04/30/2003 MECHANICAL - FINAL Partial Approval IMC 606.2.1 SMOKE ALARMS LOCATE IN RET. AIR DUCTING. CONDENSOR #3. REFRIG. PIPING. ELECT. COND. ETC.