Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2003 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000*GAS PRESS TEST OK 15 PSI. | |
| 02/13/2003 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*1.) PROVIDE SLEEVE & VENT ON GAS PIPE UNDER THE CONCRETE DECK. PROVIDE APPROVED TAPE PRIMER ON ALL TAPED JOINTS. RETEST SYSTEM. RECALL FOR INSPECTION. NOTE: DO NOT USE UNIONS TO CONNECT TO EXISTING PIPE. USE REVERSE THREAD COUPLING & NIPPLE. |