Permit: T02CM03748

Parcel: 128100810

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Permit Number - T02CM03748

Inspection Description - PLUMBING - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/23/2002 PLUMBING - ABOVE CEILING Approved IVRS - Inspection 0000*
09/09/2002 PLUMBING - ABOVE CEILING Denied IVRS - Inspection 0999*1.) ABS DWV UNDERGROUND OK WATER TEST OK TIE-IN TO EXISTING OK 2.) ABS DWV ABOVE GRADE OK WATER TEST OK OK TO TIE-IN VENT TO EXISTING OK TO COVER UNDERGROUND NOTE JUST A REMINDER TRAPS TO BE THE SAME SIZE AS THE TRAP ARM TO WHICH THEY ARE CONNECTED. ANY CHANGE WILL REQUIRE TEST AND RE-INSPECTION. 3.) PLUMBER PLEASE READ PLUMBING SPEC'S ALL HOT WATER PIPING TO BE INSULATED W/1/2" THICK FIBER GLASS INSULATION. NO PROVISION MADE IN HANGERS AND SUPPORTS TO ALLOW FOR INSULATION. GO AHEAD AND INSULATE, AND RECALL FOR INSPECTION.