Permit: T02CM03747

Parcel: 106040860

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
03/06/2003 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000*SENT TO TEP ON 3/7/03 AT 9:15AM
02/19/2003 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0215* 1) SELF TAPPING SHEET METAL SCREWS ARE NOT PERMITTED AS FASTENERS FOR ELECTRICAL TERMINALS, ETC. DRILL OUT HOLE AND USE MIN. 1/2-20 X 1/2 MACHINE BOLT WITH WASHE & NUT. SEE ART 300 NEC. THANKS 2) CUT OFF SLACK WIRES AND BEND AWAY FROM INSULATED LOAD CONDUCTORS.
02/12/2003 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0215*CORRECT THE GROUND SPLICE PROBLEM.