Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/25/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/19/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 11/15/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1.) NO LOADS CONNECTED TO PANEL MAP-A AT THIS TIME IF LOADS ARE TO BE CONNECTED PLEASE PULL PERMITS FOR WORK. 2.) JUNCTION BOX NEED RIDGID SUPPORT. PVC CONDUIT ARE SUPPORTING 1 SIDE UNISTRUT THE OTHER. PLEASE PROVIDE ANOTHER SUPPORT. 3.) PLEASE HAVE EQUIPMENT PLANS ON SITE. |
|
| 10/23/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*NOT READY 1.) WORK AT PNL. MDP INCOMPLETE. 2.) J-FRAME C/B'S NOT IN. RECALL. | |
| 10/19/2002 | ELECTRIC - FINAL | Partial Approval | 1. PANEL MDP-A WHERE FAULT CURRENT NOT CALCULATED, UNDER FUTURE PERMIT/PLAN. NOT APPLICABLE THIS PROTECT PER GARY PRICE. 2.) OK FEEDERS/POWER EXCEPT COMPACTORS, SUMP PUMPS. | |
| 10/18/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*CK CONUITS UNDERGROUND OF SLAB. 1.) PLEASE VERIFY FAULT CURRENT AT MDP -2 2.) PLEASE VERIFY PANEL BOARD MDP-1 FOR RATING. RECEIVED CHECK #6005 FOR #102.00 FOR AFTER HOURS INSPECTION. |