Permit: T02CM03742

Parcel: 103090520


Addresses:

3909 N RUNWAY DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/25/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/19/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
11/15/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) NO LOADS CONNECTED TO PANEL MAP-A AT THIS TIME IF LOADS ARE TO BE CONNECTED PLEASE PULL PERMITS FOR WORK.
2.) JUNCTION BOX NEED RIDGID SUPPORT. PVC CONDUIT ARE SUPPORTING 1 SIDE UNISTRUT THE OTHER. PLEASE PROVIDE ANOTHER SUPPORT.
3.) PLEASE HAVE EQUIPMENT PLANS ON SITE.
10/23/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*NOT READY 1.) WORK AT PNL. MDP INCOMPLETE. 2.) J-FRAME C/B'S NOT IN. RECALL.
10/19/2002 ELECTRIC - FINAL Partial Approval 1. PANEL MDP-A WHERE FAULT CURRENT NOT CALCULATED, UNDER FUTURE PERMIT/PLAN. NOT APPLICABLE THIS PROTECT PER GARY PRICE. 2.) OK FEEDERS/POWER EXCEPT COMPACTORS, SUMP PUMPS.
10/18/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*CK CONUITS UNDERGROUND OF SLAB. 1.) PLEASE VERIFY FAULT CURRENT AT MDP -2 2.) PLEASE VERIFY PANEL BOARD MDP-1 FOR RATING. RECEIVED CHECK #6005 FOR #102.00 FOR AFTER HOURS INSPECTION.