Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02CM03709
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/04/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) GAS VALVE ON FURNACE-OK 2) WATER HEATER APPLIANCE COLLAR SECURED-OK 3) PRV REMOVED NO EXP TANK REQUIRED-OK 4) DROPPED GAS CARD FOR UNIT 1 AND 2 5) BLDG FINAL APPROVED PER LEERAY | |
09/02/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/1) MUST LOCATE GAS VALVE FOR FURNACE WITHIN 3' OF REGULATOR FULL DEVELOPED LENGTH. 2) MUST SECURE APPLIANCE COLLAR FOR WATER HEATER. 3) WATER HEATERS REQUIRE AN EXPANSION TANK DUE TO CLOSE SYSTEM FROM PRV VALVE. |