Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T02CM03709
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2003 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*SENT TO TEP ON 08/07AM | |
08/04/2003 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*/ 1) NEED TO TIE IN UFER TO NEUTRAL - RUN A MAIN BOND JUMPER #2 FROM GROUND BAR TO NEUTRAL BAR. 2) SUPPORT BOTTOM OF SERVICE. 3) STRAP GROUND TO WALL. | |