Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2003 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection 0000* | |
| 02/24/2003 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000*TOP PERIMETER 4' INTERIOR. | |
| 02/04/2003 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000*1L PERIMETER. | |
| 01/29/2003 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection 0999* 1.) EXCESSIVE MORTAR FINS, @ JAMBS. 2.) JAMB BARS NOT CONTINUOUS TO FOOTING DOWELS. 3.) VERTICAL MISSING NEAR SOUTH EAST CORNER. 4.) HORIZONTAL REINFORCEMENT AROUND OPENINGS SHOULD EXTEND 24" PAST JAMB. |