Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T02CM03709

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
03/07/2003 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection 0000*
02/24/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*TOP PERIMETER 4' INTERIOR.
02/04/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*1L PERIMETER.
01/29/2003 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection 0999*
1.) EXCESSIVE MORTAR FINS, @ JAMBS.
2.) JAMB BARS NOT CONTINUOUS TO FOOTING DOWELS.
3.) VERTICAL MISSING NEAR SOUTH EAST CORNER.
4.) HORIZONTAL REINFORCEMENT AROUND OPENINGS SHOULD EXTEND 24" PAST JAMB.