Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02CM03703

Parcel: 113051820


Addresses:

3427 N WILSON AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/20/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
08/19/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) 4" CABLE TO SHOP MUST BE GFCI BREAKER 2) HORN BREAKER 2 NOT ALLOWED IN SIEMENS QP PANEL 3) UTILITY ROOM OUTLET HAS OPEN GROUND 4) ELECTRIC GFCI OUTLET REQUIRED ON COUNTER RT OF SINK 5) ALL BEDROOMS MUST HAVE AT LEAST BATTERY OPERATED SMOKE DETECTORS AND ROOMS LEADING TO BEDROOM