Permit: T02CM03694

Parcel: 10512013B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/30/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
09/26/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) PEX PLUMBING NOT PROPERLY INSTALLED TO COUPLINGS ELBOWS AND FITTINGS. PROVIDE IAPMO INSTALLATION STANDARDS FOR PEX AND COMPLY. TUBING MUST BE WITHIN 1/16" OF FITTING STOP 2) NEXT FAILURE WILL BE CHARGED A REINSPECTION FEE
09/25/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) NO DWV WATER TEST PER UPC 712.2 2) NO PRESSURE ON POTABLE WATER 3) PEX CONNECTIONS NOT PROPERLY MADE. TUBING MUST BE WITHIN 1/16" OF STOP ON CONNECTORS 4) COULD NOT LOCATE PLAN
09/24/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0950*