Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T02CM03693

Parcel: 10512013B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/30/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
09/26/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) PEX PLUMBING NOT PROPERLY INSTALLED TO COUPLINGS, ELBOWS AND FITTINGS. PROVIDE IAPMO INSTALLATION STANDARDS FOR PEX AND COMPLY. TUBING MUST BE WITHIN 1/16" OF FITTING STOP. NEXT FAILUR WILL BE CHARGED A REINSPECTION FEE
09/25/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) NO DWV WATER TEST PER UPC 712.2 2) PEX NOT PROPERLY INSTALLED. TUBING MUST BE WITHIN 1/16" OF STOP 3) NO PRESSURE TEST ON WATER 4) COULD NOT LOCATE PLAN
09/24/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0950*