Permit: T02CM03679

Parcel: 12101103E

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T02CM03679

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/24/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*ABOVE CEILING APPROVED OK TO CLEAR TEMP POWER SP #130. OK CABLE DROP. CLEARANCE FOR POWER SUBJECT TO FINAL APPROVAL OF MECH, PLUMBING APPROVALS, OK PER TRINI, JIM M.
09/20/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*SEE LAST INSP. WRITE UP.
09/19/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*1.) PROPERLY SUPPORT EMT RUNS THAT ARE RUN ACROSS STUDS ABOVE CEILING IN EXAM ROOMS 1-HOLE STRAPS SHOULD BE SEATED ON STUD. 2.) WHEN USING SIESMIC WIRES TO SUPPORT BOXES OR CONDUITS, IT MUST BE TIED OFF BOTH ENDS. 3.) MC CABLE OK GREEN FIELD LONGER THAN 6' IN LENGTH TO BE SUPPORTED WITHIN 12" EACH TERMINATION.