Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM03679
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000*ABOVE CEILING APPROVED OK TO CLEAR TEMP POWER SP #130. OK CABLE DROP. CLEARANCE FOR POWER SUBJECT TO FINAL APPROVAL OF MECH, PLUMBING APPROVALS, OK PER TRINI, JIM M. | |
09/20/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*SEE LAST INSP. WRITE UP. | |
09/19/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) PROPERLY SUPPORT EMT RUNS THAT ARE RUN ACROSS STUDS ABOVE CEILING IN EXAM ROOMS 1-HOLE STRAPS SHOULD BE SEATED ON STUD. 2.) WHEN USING SIESMIC WIRES TO SUPPORT BOXES OR CONDUITS, IT MUST BE TIED OFF BOTH ENDS. 3.) MC CABLE OK GREEN FIELD LONGER THAN 6' IN LENGTH TO BE SUPPORTED WITHIN 12" EACH TERMINATION. |