Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/29/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/28/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*SHOP AREA IS OK SHOP AREA ROUGH IN IS OK CHANGES TO GROUNDING OF SERVICE EQUIPMENT REPARIED. THE ENGINEER OF RECORD, MR GEROME SPECIFIED THE USE OF CONDUIT FOR THE ENTIRE JOB. PLAN SHEET E1 OTE FOUR 4 SPECIFIES EMT FOR THE OFFICE AREA. CORRECT & RECALL OR SECURE THE PERMISSION OF THE ENGINEER OF RECORD TO REVISE HIS SPEC'S |