Permit: T02CM03663

Parcel: 12606204A


Addresses:

630 N ALVERNON WY

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
04/21/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
04/15/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*
09/13/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245* SEE WRITE UP FROM 9-9-02
09/10/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*INSTALL ALL LIGHT FIXTURES. 2.) CONTR. TO HAVE 6' LADDER ON SITE TO SEE ABOVE CEILING.
09/09/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*ALL CAN LTS TO HAVE SIESMIC WIRES AND 4 SQUARE LAYING ON ACOUSTIC TILES TO BE INDEPENTLY SUPPORTED. 2.) MC CABLE TO BE SUPPORTED. WITHIN 12" OF TERMINATIONS TO A STRUCTURAL MEMBER NOT TO OTHER CONDUITS. 3.) UNTERMINATED MC WITH WIRES TO BE ABONDONED OR TERMINATED IN J-BOX.
09/06/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*INSTALL SIEZMEC WIRES ON 2 X 4 LAY IN FIXTURE 2 SCREWS. 2. SUPPORT MC ABOVE CEILING PER NEC.