Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/21/2003 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 04/15/2003 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245* |
| 09/13/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245* SEE WRITE UP FROM 9-9-02 |
| 09/10/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*INSTALL ALL LIGHT FIXTURES. 2.) CONTR. TO HAVE 6' LADDER ON SITE TO SEE ABOVE CEILING. |
| 09/09/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*ALL CAN LTS TO HAVE SIESMIC WIRES AND 4 SQUARE LAYING ON ACOUSTIC TILES TO BE INDEPENTLY SUPPORTED. 2.) MC CABLE TO BE SUPPORTED. WITHIN 12" OF TERMINATIONS TO A STRUCTURAL MEMBER NOT TO OTHER CONDUITS. 3.) UNTERMINATED MC WITH WIRES TO BE ABONDONED OR TERMINATED IN J-BOX. |
| 09/06/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*INSTALL SIEZMEC WIRES ON 2 X 4 LAY IN FIXTURE 2 SCREWS. 2. SUPPORT MC ABOVE CEILING PER NEC. |