Permit: T02CM03656

Parcel: 124150180


Addresses:

960 E 17TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/03/2002 ELECTRIC - SERVICE UPGRADE Approved
09/06/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*OK TO CLEAR FOR SERVICE UPGRADE. CALL FOR WHEN CHANGE OVER COMPLETE. FOR FINAL 1.) RESET GROUND LUG IN GUTTER TIT ON BOTTOM KEEP LUG FROM FULL FACE CONTACT. 2.) PLACE AN ID FOR OLD EXISTING DISCONNECT PLACE AN ID ON NEW DISCONNECT AND FEED. 4.) INSTALL PROPER SCREWS ON GUTTER. PLEASE CALL OFFICE RAY M. 791-5550. 5.) INSTALL REJECT PINS EXTENTION 1136.
09/04/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*1.) SUPPORT GROUNDING ELECTRODE CONDUCTOR TO WALL OR BURY. 110-12. 2.) BOND BUSHINGS REQUIRED BETWEEN CT CAN AND GUTTER BOTH ENDS OF NIPPLES, OR BONDING LOCKNUTS PER 250-94 NEC. 3.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE. 4.) INSTALL INSULATING BUSHINGS IN PULL BOX PER ART 300 NEC. 5.) NEUTRALS AT BOTH DISCONNECTS TO BE BONDED TO SAME GROUNDING SYSTEM.