Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
|
| 09/06/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*OK TO CLEAR FOR SERVICE UPGRADE. CALL FOR WHEN CHANGE OVER COMPLETE. FOR FINAL 1.) RESET GROUND LUG IN GUTTER TIT ON BOTTOM KEEP LUG FROM FULL FACE CONTACT. 2.) PLACE AN ID FOR OLD EXISTING DISCONNECT PLACE AN ID ON NEW DISCONNECT AND FEED. 4.) INSTALL PROPER SCREWS ON GUTTER. PLEASE CALL OFFICE RAY M. 791-5550. 5.) INSTALL REJECT PINS EXTENTION 1136. |
| 09/04/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*1.) SUPPORT GROUNDING ELECTRODE CONDUCTOR TO WALL OR BURY. 110-12. 2.) BOND BUSHINGS REQUIRED BETWEEN CT CAN AND GUTTER BOTH ENDS OF NIPPLES, OR BONDING LOCKNUTS PER 250-94 NEC. 3.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE. 4.) INSTALL INSULATING BUSHINGS IN PULL BOX PER ART 300 NEC. 5.) NEUTRALS AT BOTH DISCONNECTS TO BE BONDED TO SAME GROUNDING SYSTEM. |