Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* SENT TO TEP ON 11/14/02 AT 9:15 OK FINAL OK TO CLEAR. 11/12/02 NOTE: 1.) METAL EXTENDER RINGS NOT LISTED FOR USE. PLEASE USE AN APPROVED RING. 2.) FINISH CHECKING CLOCKWISE ROTATION OF CONDUCTORS ON TERMANALS 3.) #8 NM CABLE IS FOR ONLY L10 AMPS. |
|
| 11/12/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
| 11/10/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) AN EXTENDER RING IS NEED AT CABINET RECEPTICALES. 2.) MAINTAIN WORK CLEARENCE A/C DISCONNECTS. 3.) PLEASE INSTALL CONDUCTORS UNDER TERMANIALS IN A CLOCKWISE DIRECTION. 4.) PANEL BREAKER NEED TO BE LABELED 5.) NM CABLE #8 GOOD ONLY FOR 40 AMPS 336-26. |