Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/12/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 09/20/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 09/19/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*A CONNECTOR IS NEEDED AT EXHAUST FANS 373-5 2.) PROTECTION OF CABLES PASSING THROUGH STUDS IS NEEDED 300-4. 3.) USE AN APPROVED CONNECTOR WITH BOXES. 4.) MAINTAIN FIRE WALL SEPERATION OF ELECTRIC 300-22. 5.) A BOX MAY BE NEEDED FOR BATH LIGHTS 6.) SUPPORT CABLES ENTERING PANELS 7.) MAINTAIN WORKING CLEARENCE FOR A/C DISCONNECTS. 8.) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250-8. 9.) CLEAN SURFACE UNDER LUG 250-12. 10.) USE LISTED AND APPROVED BONDING AND LOCKING DEVICES IN GUTTER. 11.) PERMANENT METAL ADDRESS LABELS WILL BE NEEDED. 12.) 1/0 UFER WAS INSTALLED WITHOUT INSPECTION. |