Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 11/12/2002 |
ELECTRIC - UFER |
|
Approved |
IVRS - Inspection 0000* |
| 08/09/2002 |
ELECTRIC - UFER |
|
Partial Approval |
IVRS - Inspection 0000*WE HAVE 2-#4 COPPER CONNECTED TO REBAR AT NORTH & SOUTH ENDS. PLANS CALL FOR 1/0 COPPER. PLEASE HAVE A LETTER FROM ARCHITECT OR ENGINEER FOR REVISION OR INSTALL AS PER PLANS. |