Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02CM03646

Parcel: 118062660

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/06/2003 BUILDING - FINAL Approved IVRS - Inspection 0000*
02/27/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) CONDENSOR OVERFUSED 2) SEAL PENETRATION ABOVE DISCONNECT BOX AT METAL CONDUIT 3) HEAT STRIP NEEDS TO BE MARKED FOR INSTALLED UNIT 4) NEED GROUND WIRE BETWEEN HEAT PUMP AND BOOT TO METAL DUCT