Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM03638
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 07/01/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 06/09/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK WALLS 2ND FLOOR, OK CABLE DROP ONLY | |
| 06/06/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK WALLS NORTH AND NORTHWEST WING 2) FINISH EXHAUST FANS | |
| 05/23/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 05/20/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK 2" PVC PHONE BUILDING TO BUILDING 2) OK CANAPOY BETWEEN BOUDG NORTH EAST AND MAIN AND 2 ROOM ENTRYS WITH CANS 3) OK GFCI FOR ROOF A/C'S | |
| 05/06/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK GFCI'S OK 3/0 & #4 TO REBAR INTERIOR SLAB. |
|