Permit: T02CM03634

Parcel: 12110005D


Addresses:

2330 N SWAN RD

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
09/18/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
08/26/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*1.) SUPPORT MC WITHIN 12" EACH TERM. AND AT 6' INTERVALS PER 334 NEC. 2.) DO NOT USE BROWN COLOR BRANCH CIRCUIT FOR 120, 208V SYSTEM PER #9287 CITY ORDIN. 3.) BEFORE INSTALLING DEVICES & COVERS, NEED TO SEE GROUND CONNECTION IN BOXES. 4.) OK WALLS 5.) NEED PH# NAME OF L-11 LICENSED CONTR. DOING WORK.