Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/18/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 08/26/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*1.) SUPPORT MC WITHIN 12" EACH TERM. AND AT 6' INTERVALS PER 334 NEC. 2.) DO NOT USE BROWN COLOR BRANCH CIRCUIT FOR 120, 208V SYSTEM PER #9287 CITY ORDIN. 3.) BEFORE INSTALLING DEVICES & COVERS, NEED TO SEE GROUND CONNECTION IN BOXES. 4.) OK WALLS 5.) NEED PH# NAME OF L-11 LICENSED CONTR. DOING WORK. |