Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM03634
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
08/26/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) SUPPORT MC WITHIN 12" EACH TERM. AND AT 6' INTERVALS PER 334 NEC. 2.) DO NOT USE BROWN COLOR BRANCH CIRCUIT FOR 120, 208V SYSTEM PER #9287 CITY ORDIN. 3.) BEFORE INSTALLING DEVICES & COVERS, NEED TO SEE GROUND CONNECTION IN BOXES. 4.) OK WALLS 5.) NEED PH# NAME OF L-11 LICENSED CONTR. DOING WORK. |