Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM03629
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2002 | ELECTRIC - ABOVE CEILING | Approved | ||
10/18/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OK TO TILE EXCEPT AS NOTED 1.) NEED TO SEE SUPPORT WIRES FOR HUBEL BOXES AFTER SET IN PLACE. | |
10/17/2002 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000* | |
10/16/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*SUPPORT DATA UP OFF OF GRID AS PER CODES. 2.) SUPPORT FLEX CONDUIT AS PER CODE. 3.) SUPPORT TRACK FIXTURES AS PER CODE 4.) FIXTURES TO BE ATTACHED TO GRID 5.) OPEN JUNCTION BOXES. 6.) PLEASE FILL UNUSED OPENINGS IN JUNCTION BOXES. 7.) ALL METAL BOX TO BE GROUNDED. 8.) SUPPORT CONDUIT AS PER CODE. 9.) SUPPORT M/C CABLE AS PER CODES. 10.) HUBBEL BOX TO BE ATTACHED TO GRID AND SUPPORTED UP AS PER CODES. |