Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM03620
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
12/12/2002 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) SHEAR TRANSFER NOT DONE ON SW2 WALLS 2) NEED ANSWER ON ELECTRIC FURNACE WATER HEATER 2) BANG PLATE AT LAV REVENT SHEAR SIDE 4) 48" ON CENTER GABLE BRACES 5) 2" CLEARANCE TO FIREPLACE FLUE | |
12/09/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) HD'S AT ENTRY WAY NUTS LOOSE NO EPOXY AND AT MASTER BATH 2) REPAIR SHEAR AT BEDROOM 3) FIREBLOCK AT MECHANICAL ROOM 4) DWV'S NO TEST | |
12/03/2002 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) LEAK AT TUB | |
11/14/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) DWV TEST FAILED 2) SECURE TOP OF FIREPLACE FLUE MINIMUM 1" FROM COMBUSTIBLES 3) COMPLETE STUCCO MESH AND LOAD ROOF BEFORE RE-CALL |