Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/21/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*/ 1) CORRECTIONS MADE OK 2) ABS THRU ROOF-OK CLOSET FLANGES-OK 3) OK TO COVER WALLS | |
| 01/17/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) PROVIDE LISTING FOR PLUMBERS TAPE NOT APPROVED STRAP. 2.) WHEN YOU NOTCH THE BOTTOM OR TOP PLATE AN FHA STRAP IS USED TO TIE THAT MEMBER BACK INTO ITSELF A NAIL GUARD DOES NOT PROVIDE THE SAME STRENGTH AND PROTECTION OF THE AFFECTED MEMBER. 3.) CLOSET BENDS ARE NOT SECURE 4.) REED ALL OF THE CORRECTIONS ABOVE AND COMPLY. 5.) NO WATER TEST ON ABS. 6.) WHERE ARE YOU CLEAN OUTS WHERE THE BLDG DRAIN CONNECTS TO BLDG SEWER. |
|
| 01/12/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1.) OK TO COVER YARDWATER PIPING. 2.) ISOLATE COPPER LINES TOUCHING. COPPER WIRE NOT APPROVED STRAP. SEE TABLE 3-1 94 UPC HANGERS AND SUPPORTS. 3.) WATER TEST ON ABS DWV THRU ROOF OK 4.) NEED TO SEE CLOSET FLANGES 5.) TUBS OK 6.) USE FHA STRAP NOT NAIL GUARD ON BOTTOM PLATE. |