Permit: T02CM03590

Parcel: 118220290


Addresses:

138 W 24TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/19/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/07/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* 1) UNUSED OPENINGS IN SERVICE PANELS NOT PLUGGED PROPERLY - RAIN WATER CAN STILL ENTER PANEL - USE APPROVED KO PLUGS LISTED FOR OUTDOOR USE. PLUG BREAKER SPACE ON FRONT.
04/16/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 138 W. 24TH ST. - NOTES: 1) COOLER CORDS STILL HAVE OPEN SPLICES. 2) PLUG UNUSED OPENINGS IN SERVICE PANEL. 3) INSTALL COVERS ON OPEN J-BOXES INSIDE. / 140 W. 24TH ST APPROVED.
04/14/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 1) INSTALL ADDRESS LABEL ON 138 AND OTHER 2) REPLACE COOLER CORDS WITH UNSPLICED CORDS 3) INSTALL ADDRESS NUMBERS ON UNITS 4) UNIT LOCKED RE-CALL WHEN OPEN
03/11/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ OK FINAL #140 ONLY. OTHER INSP. STILL NEED TO FINAL/
03/10/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ NOT ALL CORRECTIONS MADE - SEE LIST FROM PREVIOUS INSP.
03/08/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) ADDRESS SERVICE. 2) 30 A. 2 POLE FOR DRYER GE, 20A CUTLER HAMMER TO BE GE.3) SMOKE DETECTORS TO BE ELECTRIC AND BATTERY. 4) OUTDOOR FRONT RECEPTACLE MISSING. 5) SEVERAL OUTLET BOXES NOT GROUNDED. 6) SIDE AND REAR EXITS TO HAVE GFI RECEPTACLES. 7) COOLER NEEDS SUPPORT.