Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
Permit Number - T02CM03571
Inspection Description - BUILDING ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/06/2002 | BUILDING ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
09/05/2002 | BUILDING ABOVE CEILING | Denied | IVRS - Inspection 0999*1.) SEE ATTACHED ASTM C636 STANDARD 2.3.3. NO KINKS OR BENDS IN WIRES TO PROVIDE LEVELING 2.3.4. FIGURE 1-3 TURES IN 3" 2.1.3 SPACE HANGERS 4 FT O.C. MAXIMUM. | |
09/04/2002 | BUILDING ABOVE CEILING | Denied | IVRS - Inspection 0999*1.) INSTALL CEILING GRID PER ASTEM & CISCA STANDARDS. A.) WIRES 4' ON CENTER MAXIMUM BOTH DIRECTIONS. B.) WIRES TO BE TO TWISTED 3 FALL TURNS WITHIN 3" |