Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000*/ 1) AT FINAL IF HOUSE IS COPPER WATER LINES INSTALL WATER BOND, IF PLASTIC LABEL PANEL AS SUCH NOT WATER BONDED SYSTEM |
| 09/17/2002 |