Permit: T02CM03527

Parcel: 12315340A


Addresses:

1003 E ELM ST


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T02CM03527

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
10/03/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*/ 1) AT FINAL IF HOUSE IS COPPER WATER LINES INSTALL WATER BOND, IF PLASTIC LABEL PANEL AS SUCH NOT WATER BONDED SYSTEM
09/17/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*/ 1) NO GROUND WIRE INSTALLED. UFER TOO SHORT EITHER CAD WELD OR INSTALL TWO GROUND RODS. 8 FEET LONG 6 FEET APART CONNECTED TO PANEL WITH #4 CONDUCTOR 2) PUT ADDRESS ON PANEL 3) DISCONNECT ALL CIRCUITS AND INSTALL A MAINTENANCE 20 AMP GFCI OUTLET