Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T02CM03527
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/03/2002 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*/ 1) AT FINAL IF HOUSE IS COPPER WATER LINES INSTALL WATER BOND, IF PLASTIC LABEL PANEL AS SUCH NOT WATER BONDED SYSTEM | |
09/17/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*/ 1) NO GROUND WIRE INSTALLED. UFER TOO SHORT EITHER CAD WELD OR INSTALL TWO GROUND RODS. 8 FEET LONG 6 FEET APART CONNECTED TO PANEL WITH #4 CONDUCTOR 2) PUT ADDRESS ON PANEL 3) DISCONNECT ALL CIRCUITS AND INSTALL A MAINTENANCE 20 AMP GFCI OUTLET |