Date Description Inspector Results Comments
08/23/2002 FRAMING Approved IVRS - Inspection 0000*/ 1) OK TO DRYWALL
08/20/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) SMOKE DETECTORS MUST BE INNER CONNECTED TO ALL TRIP WHEN ONE GOES OFF. REQUIRES 14-3 G BETWEEN UNITS 2) SMOKE DETECTOR NOT ALLOWED WITHIN 36" OF AIR REGISTER (HALL) 3) PEX PLUMBING NOT ALLOWED WITHIN 12" OF RECESSED LIGHT 4) DRYER VENT MUST EXHAUST OUTSIDE