Permit: T02CM03522

Parcel: 11006015C

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/22/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*
CORRECTIONS HAVE BEEN MADE AS PER LAST REQUEST FINAL OK S.T.O.I.
12/20/2002 PLUMBING - FINAL Denied 1.) WATER CLOSET HANDLES MUST BE ON OPEN SIDE.
2.) WATER CLOSET SEATS MUST BE OPEN FRONT
3.) HC. LAVATORY WATE & SUPPLYS MUST BE WRAPPED.
4.) H.C. LAVATORYS DO NOT MEET ADA MIN.
HEIGHT FROM FINISH FLOOR TO BOTTOM OF COUNTER TOP.
5.) PROVIDE LISTING FOR H.C. LAVATORY FAUCETS
6.) SINK IN LOUNGE MUST HAVE A C.O.
7.) WATER HTR REQUIRES A EXPANSION TANK P & T DRAIN CAN NOT HAVE A FLEX LINE