Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 12/24/2002 | ELECTRIC - FINAL | Partial Approval | 1.) PLEASE RETYPE CORRECTED PANEL DIRECTORIES. 2.) GROUNDING EQUIPMENT CONDUCTORS TO BE SIZED PER 250-122. AT A/C DISCONNECTS OK TEMP C OF O SUBJECT TO DETERMANATION OF INSPECTION MANAGER. |
|
| 12/23/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* 1.) FINISH WATER HEATER INSTALLATION 2.) EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" FROM BOX TO DEVICE. 3.) PANEL SCHEDULE TO MATCH PANEL ALSO PLEASE LABEL ON OUTSIDE COVER OF PANEL. 4.) INSTALL FLOOR BOX DEVICES & COVERS. 5.) FINISH INSTALLATION OF CAN RIMS 6.) LOOSE FITTINGS AT A/C DISCONNECTS 7.) BOND A/C DISCONNECT ENCLOSURES. 8.) LABEL DISCONNECTS. |
|
| 12/20/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 12/04/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) DATA TO BE SUPPORTED UP OFF OF GRID ALSO NOT TO BE OFF OF CEILING WIRES. 2.) SUPPORT WIRES TO BE IN OPPISITE DIRECTIONS 3.) MISSING EXIT SIGN & SUPPORT WIRE. 4.) MISSING FIXTURES. |