Permit: T02CM03518

Parcel: 108214640

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/13/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/24/2002 ELECTRIC - FINAL Partial Approval 1.) PLEASE RETYPE CORRECTED PANEL DIRECTORIES.
2.) GROUNDING EQUIPMENT CONDUCTORS TO BE SIZED PER 250-122. AT A/C DISCONNECTS
OK TEMP C OF O SUBJECT TO DETERMANATION OF INSPECTION MANAGER.
12/23/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
1.) FINISH WATER HEATER INSTALLATION
2.) EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" FROM BOX TO DEVICE.
3.) PANEL SCHEDULE TO MATCH PANEL ALSO PLEASE LABEL ON OUTSIDE COVER OF PANEL.
4.) INSTALL FLOOR BOX DEVICES & COVERS.
5.) FINISH INSTALLATION OF CAN RIMS
6.) LOOSE FITTINGS AT A/C DISCONNECTS
7.) BOND A/C DISCONNECT ENCLOSURES.
8.) LABEL DISCONNECTS.
12/20/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
12/04/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) DATA TO BE SUPPORTED UP OFF OF GRID ALSO NOT TO BE OFF OF CEILING WIRES.
2.) SUPPORT WIRES TO BE IN OPPISITE DIRECTIONS
3.) MISSING EXIT SIGN & SUPPORT WIRE.
4.) MISSING FIXTURES.