Inspection Status: Approved
Inspection History: OUTDOOR LIGHTING FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/20/2003 |
OUTDOOR LIGHTING FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/18/2003 |
OUTDOOR LIGHTING FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/22/2003 |
OUTDOOR LIGHTING FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ OK 3/4" PVC IN PARKING LOT AND NORTH TO SOUTH AS MARKED. |
| 07/21/2003 |
OUTDOOR LIGHTING FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CONDUIT IN PARKING LOT NOT INSPECTED. CONDUIT TO BE 24" AS PER 300-5. OK (5) POLE BASES AS MARKED. OK PVC CONDUIT AS MARKED. RECEIVED LETTER FOR PVC 90 DEGREES. |
| 07/18/2003 |
OUTDOOR LIGHTING FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PLANS CALL FOR RIGID STEEL ELBOW - WE HAVE PVC. 2) GROUNDING ELECTRODE CONDUCTOR TO BE STRAIGHT DOWN WITH COIL W BOTTOM OF BASE. |