Date Description Inspector Results Comments
06/26/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) OK ROUGH ELECTRIC
06/24/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) FINISH WIRING-WIRE HANGING 2) SUPPORT "SE" CABLE AT SERVICE 3) SUPPORT CABLES ABOVE PANEL AND FINISH BELOW 4) WHERE ARE FEEDERS TO PANELS 5) SUPPORT NM WITH IN 12" RECESSED CANS AND CEILING BOXES 6) IS POWER NEEDED FOR SPRINKLER CONTROLS ?
06/09/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK EXTERIOR WALKWAY LID