Permit: T02CM03493

Parcel: 106060180


Addresses:

1354 W PRINCE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM03493

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/25/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OKAY FOR C OF O.
10/24/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*AS PER REVISION EXIST SW REMAINS, REAR DOOR TO STAY SHUT. 2.) HIGH LEG ON SUB PANEL NEED TO BE ON B PHASE 384 NEC. 3.) INSTALL GREEN GROUND SCREW AT SUB PANEL. 4.) WILL NEED ACCESS TO AC OR MECH TO CHECK.