Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM03493
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/22/2002 | ELECTRIC - ABOVE CEILING | Approved | MC USED AS FIXTURE WHIPS LONGER THAN 6' IN LENGTH TO BE SUPPORTED WITHIN 12" EACH TERMINATION. 2.) NEED TO SEE REVISED DRAWING. | |
10/21/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*MC USED AS FIXTURE WHIPS LONGER THAN 6' IN LENGTH TO BE SUPPORT WITHIN 12" EACH TERMINATION. 2.) NEED TO SEE REVISED DRAWING. |