Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* 1.) GAS PRESSURE IS OK 2.) PLBG. FINAL IS OK 3.) OK FOR C OF O. |
|
| 12/12/2002 | PLUMBING - FINAL | Denied | 1.) GAS IS NOT INSTALLED PER PLAN PROVIDE APPROVED GAS ISOMETRIC. 2.) ABS MAY NOT BE RUN IN AN EXPOSED EXTERIOR LOCATION. 3.) INDIRECT WASTE PIPING NOT TO CODE. 4.) YOU MUST COMPLY WITH ALL CORRECTIONS FROM 12/10/02. 5.) WE DO NOT SUPPLY PUNCH LISTS FOR PLUMBER HAVE HIM CHECK ALL WORK. 6.) HAVE PLUMBER REVIEW GENERAL NOTES. |
|
| 12/10/2002 | PLUMBING - FINAL | Denied | 1.) TRIPLE COMPT. SINK REQUIRES A P-TRAP. AND C.O. CONT. WASTE EXCEEDS 135 CHANGE OF I DIRECTION. 2.) MUST ANCHOR 2" WASTE LINE FOR TRI COMPT. SINK. 3.) 3" WASTE LINE FOR GREASE TRAP EXCEEDS 135 4.) 2" C.O. FOR MOP SINK AND HAND SINK MUST HAVE 12" OF CLEARANCE TO FRONT OF C.O. 5.) INDIRECT WASTE FOR DISHWASHER HORIZONTAL 90 MUST BE L-SWCEPS AND MUST BE TRAPED WHEN LONGER THAN 5'-0". 6.) FLOW CONTROL FOR GREASE TRAP MUST BE LOCATED AS CLOSE AS POSSIBLE TO 3 COMPT SINK 7.) TRAP ARM 1 FOR HAND SINK MUST BE 1 1/2" MAX OR 2" P-TRAP. 8.) WATER HTR REQUIRES A EXPANSION TANK. |