Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T02CM03442
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/03/2002 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
11/25/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*/ 1) SEE 11/21/02 WRITE UP | |
11/22/2002 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection 0000*/ 1) PARTIAL PENDING CORRECTION DT ITEMS 4,5 AND 11 | |
11/21/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*/ 1) GROUND RODS MUST BE DRIVEN 8' INTO SOIL 2) GROUND CONDUCTOR FOR 200 AMP PANEL MUST BE MINIMUM SIZE #4 3) NO PRIOR INSPECTION REPORTS/PLAN OR PERMIT ON SITE STOPPED INSPECTION 4) TRENCH MUST BE DEEP ENOUGH FOR 24" COVER OF CONNECTORS | |
11/20/2002 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection 0000*/ 1) LABEL EACH PANEL, FOR MAIN DISCONNECT USE, (EXAMPLE) (1714 E. EDISON MAIN HOUSE AND APT.) AT OUR BLDG 2) CLEAN UP WIRING IN PANEL 3) INSTALL #6 BARE CU GROUNDING CONDUCTOR FROM GRD RODS TO GRD LUG IN SERVICE. MOVE #8 NEUTRAL WIRE TO GRD. BUSS 4) INSTALL ROMEX CONNECTOR AT GRD AND BOND WIRE 5) CONDUITS FROM EXISTING CIRCUITS TO HAVE LOCK WASHERS 6) REMOVE METAL FROM CONCENTRIC 7) CHECK ALL WIRE SIZE TO MATCH BREAKER SIZE MUST BE COMPATIBLE (SEE BELOW) 8) BOND GAS AND WATER LINE 9) INSULATING BUSHING NOT SECURED ON PANEL WIRING FROM HOUSE THRU BACK OF PANEL 10) LABEL ALL CIRCUITS 11) PUT UP A BARRIER AT SERVICE TO KEEP PEOPLE AWAY FROM OPEN TEMP. WIRES 12) SECURE FEEDER (TEMP) TO WALL AS A RESTRAINT |