Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02CM03442

Parcel: 113110640


Addresses:

1714 E EDISON ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM03442

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/07/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
10/04/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
09/12/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0950*
09/03/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) 220 VAC OUTLET NOT ALLOWED/NOT PER PLAN 2) ALL WIRES MUST TERMINATE IN APPROVED-ACCESSIBLE JUNCTION BOXES 3) 110 VAC CONVENIENCE OUTLET REQUIRED WITHIN 6" OF EITHER SIDES OF DOORS 4) SECURE NMC (ROMEX) WITHIN 8" OF ELECTRIC BOXES 5) VERIFY IF COOKING IS ALLOWED IN GUEST ROOM 6) HEAT PUMP MUST BE ON DEDICATED CIRCUIT 7) METAL ELECTRIC BOXES REQUIRE ROMEX CLAMP OR BUSHINGS 8) GROUND ALL METAL ELECTRIC BOXES 9) ALL SWITCHES MUST BE GROUNDED 10) NAIL PROTECT ALL WIRES WITHIN 1 1/4" OF STUD FACE
08/28/2002 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*