Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM03442
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/07/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
10/04/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
09/12/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0950* | |
09/03/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) 220 VAC OUTLET NOT ALLOWED/NOT PER PLAN 2) ALL WIRES MUST TERMINATE IN APPROVED-ACCESSIBLE JUNCTION BOXES 3) 110 VAC CONVENIENCE OUTLET REQUIRED WITHIN 6" OF EITHER SIDES OF DOORS 4) SECURE NMC (ROMEX) WITHIN 8" OF ELECTRIC BOXES 5) VERIFY IF COOKING IS ALLOWED IN GUEST ROOM 6) HEAT PUMP MUST BE ON DEDICATED CIRCUIT 7) METAL ELECTRIC BOXES REQUIRE ROMEX CLAMP OR BUSHINGS 8) GROUND ALL METAL ELECTRIC BOXES 9) ALL SWITCHES MUST BE GROUNDED 10) NAIL PROTECT ALL WIRES WITHIN 1 1/4" OF STUD FACE | |
08/28/2002 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* |