Permit: T02CM03442

Parcel: 113110640


Addresses:

1714 E EDISON ST


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T02CM03442

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2002 ELECTRIC - UNDERGROUND Approved IVRS - Inspection 0000*/ 1) CHANGE TPR VALVE FLEX TO SOLID PIPE
11/12/2002 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*/ 1) YOU MUST HAVE AN ELECTRIC SERVICE UPGRADE PERMIT FOR CHANGING THE SERVICE PANEL ON THE MAIN HOUSE 2) EACH HOUSE MUST HAVE SEPARATE GROUNDING SYSTEMS CONSISTING OF TWO EACH 8' LONG GROUND RODS PLACED IN EXCESS OR 6' APART CONNECTED TO THE SERVICE/OR SUB PANEL WITH A CONTINOUS #4 GROUND CONDUCTOR TO EACH PANEL 3) TRENCH MUST BE AT LEAST 26" DEEP TO ALLOW FOR 24" OF EARTH COVER 4) WATER HEATER T & P LINE MUST EXHAUST DOWN BETWEEN 6" AND 18" FROM GRADE
11/10/2002 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*/ 1) FLEX PIPES AREN'T ACCEPTABLE-USE APPROVED PIPING 2) GROUND WIRE ? BE ATTACHED IN PANEL BEFORE UNDERGROUND DROP IS APPROVED