Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T02CM03442
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2002 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection 0000*/ 1) CHANGE TPR VALVE FLEX TO SOLID PIPE | |
11/12/2002 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0999*/ 1) YOU MUST HAVE AN ELECTRIC SERVICE UPGRADE PERMIT FOR CHANGING THE SERVICE PANEL ON THE MAIN HOUSE 2) EACH HOUSE MUST HAVE SEPARATE GROUNDING SYSTEMS CONSISTING OF TWO EACH 8' LONG GROUND RODS PLACED IN EXCESS OR 6' APART CONNECTED TO THE SERVICE/OR SUB PANEL WITH A CONTINOUS #4 GROUND CONDUCTOR TO EACH PANEL 3) TRENCH MUST BE AT LEAST 26" DEEP TO ALLOW FOR 24" OF EARTH COVER 4) WATER HEATER T & P LINE MUST EXHAUST DOWN BETWEEN 6" AND 18" FROM GRADE | |
11/10/2002 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0999*/ 1) FLEX PIPES AREN'T ACCEPTABLE-USE APPROVED PIPING 2) GROUND WIRE ? BE ATTACHED IN PANEL BEFORE UNDERGROUND DROP IS APPROVED |