Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/12/2002 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/09/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) YOU MUST DRIVE THE GROUND COMPLETLY 2) THE DEAD FRONT MUST BE INSTALLED CORRECTLY 3) YOU MUST RE-CALL THIS INSPECTION WHEN COMPLETE |
| 12/04/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) HOT/NEUTRAL REVERSED AT KITCHEN RIGHT OF SINK 2) DRIVE GROUND ROD DOWN TO FULL PENETRATION 3) INSTALL DEAD FRONT ON ELECTRIC PANEL |
| 12/03/2002 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 11/05/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0950* |