Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM03426
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
09/06/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) POST CAP REQUIRED AT GARAGE GLU LAM 2) PROVIDE 18 GUAGE STRAP AT OVERBORED TOP PLATE GARAGE WEST WALL 3) POSSIBLE LEAK AT 2ND FLOOR BATH 4) NAIL EXTERIOR WALLS 2ND FLOOR BOTTOM PLATE TO FLOOR CHECK THRUOUT 12" ON CENTER 5) NAIL SHEARWALL TRANSFER 2ND FLOOR BOTTOM PLATE 8" ON CENTER PER PLAN A-8/9 |