Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02CM03423
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
12/10/2002 | PLUMBING - FINAL | Denied | NO HUB COUPLINGS ARE NOT APPROVED WHEN CONNECTING ABS TO C.I. OR GALX. 2.) MUST CAULK HAND & LUNDRY SINK 3.) LAVORY SINK REQUIRES A VACCUM BREAKER @ FAUCET. 4.) ICE MACHINE REQUIRES A BACKFLOW PREVENTER 007 TESTED & CERTIFIED @ TIME OF INSPECTION. 5.) INDIRECT WASTE FOR 3 COMPT. SINK MUST BE ANCHORED AND REQUIRES A 1" AIR GAP. 6.) FUNNEL DRAIN @ WATER TABLE REQUIRES TRAP PRIMER 7.) HORIZONTAL VENT @ WATER TABLE REQUIRES A HANGER. 8.) FUNNEL DRAIN TRAP ARM DOSE NOT MEET MIN LENGTH. |