Permit: T02CM03423

Parcel: 107110090

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T02CM03423

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/12/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*
12/10/2002 PLUMBING - FINAL Denied NO HUB COUPLINGS ARE NOT APPROVED WHEN CONNECTING ABS TO C.I. OR GALX.
2.) MUST CAULK HAND & LUNDRY SINK
3.) LAVORY SINK REQUIRES A VACCUM BREAKER @ FAUCET.
4.) ICE MACHINE REQUIRES A BACKFLOW PREVENTER 007 TESTED & CERTIFIED @ TIME OF INSPECTION.
5.) INDIRECT WASTE FOR 3 COMPT. SINK MUST BE ANCHORED AND REQUIRES A 1" AIR GAP.
6.) FUNNEL DRAIN @ WATER TABLE REQUIRES TRAP PRIMER
7.) HORIZONTAL VENT @ WATER TABLE REQUIRES A HANGER.
8.) FUNNEL DRAIN TRAP ARM DOSE NOT MEET MIN LENGTH.