Permit: T02CM03423

Parcel: 107110090

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T02CM03423

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
11/29/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*SENT TO TEP 12/2/02 AT 9:15AM OK TO CLEAR/OK CABLE DROP.
11/27/2002 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection 0000*
1.) CABLE DROP SERVICE HAS NO GROUND SYSTEM ONLY BLDING AND WATER BOND NEED 2 GROUNDS RODS 6' APART.
2.) LABEL SERVICE WITH ADDRESS AND A & B PNLS.
3.) REMOVE GAS METER IN FROM OF PNL B DISCONNECT.
4.) WHERE ARE CLASS R FUSES AND INSTALL PINS.