Inspection History: ELECTRIC - CABLE DROP
Permit Number - T02CM03423
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2002 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*SENT TO TEP 12/2/02 AT 9:15AM OK TO CLEAR/OK CABLE DROP. | |
11/27/2002 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection 0000* 1.) CABLE DROP SERVICE HAS NO GROUND SYSTEM ONLY BLDING AND WATER BOND NEED 2 GROUNDS RODS 6' APART. 2.) LABEL SERVICE WITH ADDRESS AND A & B PNLS. 3.) REMOVE GAS METER IN FROM OF PNL B DISCONNECT. 4.) WHERE ARE CLASS R FUSES AND INSTALL PINS. |