Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/28/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 08/26/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*1.) SUPPORT J-BOXES ABOVE PARTITION WALLS PER NEC. 2.) ALL WIRING TO BE IN RACEWAYS PER NOTES E-2 PLANS. AC UNITS WIRED IN ROMEX. 3.) TIE UP FIXTURE WHIPS AND OR MC CABLE LAYING ON CEILING GRID. 4.) MC CABLE TO BE SUPPORTED WITHIN 12" EACH TERMINATION PER NEC. 5.) PLUG UNUSED KO IN 24 X 24 J-BOX. |