Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2004 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :*/CORRECTIONS MADE OK. OK TO COVER. | |
| 09/22/2004 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :*/1)BACK PITCHED SECTION AT WYE? BETWEEN 545, 547. OK TO COVER THE REST. | |
| 09/20/2004 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/19/2004 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | UNABLE TO LOCATE PLAN OR PERMIT CORRECT ALL BACKPITCHED SECTIONS REPLACE ALL UV DAMAGED PIPE |
|
| 05/15/2004 | PLUMBING - SEWER HCS CONNECT | Partial Approval | CORRECTIONS MADE OK 2.) OK TO BACKFILL. |
|
| 04/30/2003 | PLUMBING - SEWER HCS CONNECT | Denied | I REITERVATE THE MINIMUM REQUIRED CLEAN OUT FOR 6" ABS IS 3 1/2" 3" CLEAN OUTS INADEQUETE. | |
| 04/24/2003 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection 0999*NOT INSTALLED PER APPROVED PLAN. MINIMUM SIZE CLEANOUT FOR 6" DRAIN IS 3 1/2". PLAN CALL FOR 6" DIRECTIONAL CLEAN OUTS YOU HAVE INSTALLED 3" 2 WAY CLEAN OUT. | |
| 02/25/2003 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection 0000* NOT READY SUPER ON JOB NO APPROVED SITE SEWER PLAN ON JOB PLESE PROVIDE APPROVED DRAWING WITH SIZE OF LINE AND ALL BRANCHES. |