Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2004 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :*/CORRECTIONS MADE OK. OK TO BACKFILL. | |
| 09/22/2004 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :*/BACK PITCHED SSECTIONS AT 545, 547 CONFLUENCE. OK TO BACKFILL SEWER | |
| 09/20/2004 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/19/2004 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | UNABLE TO LOCATE PLAN OR PERMIT CORRECT ALL BACKPITCHED SECTIONS REPLACE ALL UV DAMAGED PIPE |
|
| 05/15/2004 | PLUMBING - SEWER HCS CONNECT | Partial Approval | CORRECTIONS MADE OK WATER TEST OK 2.) OK TO BACKFILL. |
|
| 04/30/2003 | PLUMBING - SEWER HCS CONNECT | Denied | I REITERATE THE MINIMUM REQUIRE CLEAN OUT SIZE FOR 6" ABS IS 3 1/2" 3" CLEAN OUTS ARE INADEQUETE. | |
| 04/24/2003 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection 0999*NOT INSTALLED PER APPROVED PLAN CALLS FOR 6' CLEAN OUTS. | |
| 02/25/2003 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection 0000* |