Permit: T02CM03405

Parcel: 11105153A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T02CM03405

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/27/2002 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*
12/23/2002 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*1.) NO FLEX ON DRYER VENTS. USE SOLID PIPE.
2.) 4" DIAMETER VENT NOT ADEQUATE ON KITCHEN EXHAUST.
3.) PROVIDE RELIEF AIR FOR DRYER ENCLOSURE CONDENSATE WILL BE EXPOSED ON ROOF. RECALL FOR INSPECTION.