Permit: T02CM03405

Parcel: 11105153A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM03405

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/06/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/30/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) WE HAVE MULITPOLE TERMANANTIONS AT GROUND BAR IN METER SECTION/PARK
2.) YOU CAN NOT PASS THRU OR SPLICE IN METER SECTION/PACK.
3.) ALL BOXES TO BE ACCESSABLE.
4.) AMPACITY FOR #8 NM CABLE TO BE PER CODE 336-26.
5.) BATH FIXTURE TO BE LISTED AND LABELED WE HAVE EXPOSED CONDUCTORS IN COMBUSTABLE MATERIAL AND AN OPEN JUNCTION BOX.
6.) CLOSET LIGHT FIXTURE TO MAINTAIN CLEARENCES AS PER 410-8.
7.) TIGHTEN WATER HEATER FITTING AND A DISCONNECTING MEANS IS NEEDED.
8.) TIGHTEN LOOSE FITTING FOR A/C UNIT AND MAINTAIN WORKING CLEARENCES TIGHTEN TERMANATIONS OF CONDUCTORS.