Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM03405
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/06/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/30/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) WE HAVE MULITPOLE TERMANANTIONS AT GROUND BAR IN METER SECTION/PARK 2.) YOU CAN NOT PASS THRU OR SPLICE IN METER SECTION/PACK. 3.) ALL BOXES TO BE ACCESSABLE. 4.) AMPACITY FOR #8 NM CABLE TO BE PER CODE 336-26. 5.) BATH FIXTURE TO BE LISTED AND LABELED WE HAVE EXPOSED CONDUCTORS IN COMBUSTABLE MATERIAL AND AN OPEN JUNCTION BOX. 6.) CLOSET LIGHT FIXTURE TO MAINTAIN CLEARENCES AS PER 410-8. 7.) TIGHTEN WATER HEATER FITTING AND A DISCONNECTING MEANS IS NEEDED. 8.) TIGHTEN LOOSE FITTING FOR A/C UNIT AND MAINTAIN WORKING CLEARENCES TIGHTEN TERMANATIONS OF CONDUCTORS. |