Permit: T02CM03405

Parcel: 11105153A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM03405

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/23/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
12/20/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
INSPECTOR WILL LOOK IN BOXES AFTER ROCK INSTALLED IF NOT IN COMPLIANCE WITH NOTE #2 ROCK.
12/17/2002 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
12/13/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*NOTES 1.) ROMEX IN CIELING AREAS NOT SUPPORTED PER NEC.
2.) SEE ITEM #1 EAST INSPECTION WRITE UP.
3.) NEED TO VERIFY NAME & PH# OF LICENSED ELECTRICAL CONTR. DOING WORK.
4.) REVISE PLANS TO INDICATE TYPE OF SERVICE EQUIP. USE. PLANS SHOW A SINGLE METER ALL IN ONE, 125A. DUAL PACK 200AMP INSTALLED.
12/09/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) OK
ITEM #2 - 1999 NEC ARTICLE 370-17-C ROMEX SHEATH SHALL EXTEND INTO BOX LIMIT 1/4" PLUS SOME OK NOT ALOT. #3 OK
#4 ROMEX CONNECTORS TO BE USED ONLY FOR THE LISTEN AMOUNT OF CABLES EACH CAN HOLD THERE IS NO APPROVAL FOR A CONNECTOR TO ALLOW AS MANY LABELS AS POSSIBLE 110-3 B USE EQUIPMENT AS LISTED. NOT IN BUT OK TO COVER FIRE WALL SUBJECT TO OTHER INSPECTIONS.
12/04/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
1.) FINISH MAKE UP OF BOXES EVEN WHERE YOU HAVE ONE CABLE.
2.) PLEASE TO MUCH COVERING OF ROMEX INTO BOXES, LIMIT TO APPROX. 1/4"
3.) USE ROMEX CONNECTOR IN LIEU OF K.O. BUSHING.
4.) K.O. BUSHING AT TOP OF PANEL USE ROMEX CONNECTORS.
5.) FIRE WALL PENETRATIONS SUBJECT TO BUILDING INSPECTOR.