Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T02CM03373
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/03/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1.) SOIL WATER TEST IS OK 2.) OVERHEAD WATER DISTRIBUTION IS OK 3.) OK FOR DRYWALL. |
|
01/29/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) 2" HORIZONTAL COPPER IN WALL HAS NOT BEEN SECURED 2) I BELIEVE THERE IS AN UNSUPPORTED HORIZONTAL SECTION OF ABS ABOVE CEILING, BUT CANNOT VERIFY BECAUSE INSULATION IS COVERING THE PIPE | |
01/28/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
01/27/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) SEE 103.5.1 94 UPC SECOND SENTENCE. NO PORTION OF ANY PLUMBING SYSTEM SHALL BE CONCEALED UNTIL INSPECTED AND APPROVED. INSULATION HAS COVERED PERTINENT SECTIONS REQUIRING INSPECTION. 2.) COPPER IN WALLS STILL NOT SUPPORTED. 3.) UNABLE TO SEE HORIZONTAL ABS AS IT IS COVERED BY INSULATION. |
|
01/21/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) SUPPORT COPPER IN THE WALLS 2) SUPPORT HORIZONTAL ABS 3) NO WATER TEST ON ABS 4) WASTE FOR LAVATORY EXCEEDS ALLOWABLE SIZE TRAP TO BE SAME SIZE AS TRAP ARM TRAP MAY BE ONLY ONE PIPE SIZE LARGER THAN TAIL PIECE, LARGE TAIL PIECE = 1 1/4" THEREFORE TRAP AND TRAP ARM MAY BE NO LONGER THAN 1 1/2" |